Have a personal or library account? Click to login
The Influence of Compensatory Regime of Operation of Pump Hydropower Plant Capljina on Voltage Conditions in Electric Power System of Bosnia and Herzegovina Cover

The Influence of Compensatory Regime of Operation of Pump Hydropower Plant Capljina on Voltage Conditions in Electric Power System of Bosnia and Herzegovina

Open Access
|Oct 2022

Abstract

The paper presents the results of testing the operational capabilities of the pump hydropower plant (PHPP) Capljina in compensatory, under excited mode in real time, and answers the questions how, and to what extent, the operation of PHPP Capljina in the under excited mode affects the improvement of voltage conditions in the power system of B&H. The test was performed with one machine in compensatory under excited mode with the takeover of reactive power in the amount of 160 MVAr, in a period of 4 hours. During the test, thermal power plant (TPP) Gacko operated in the maximum under excited mode for a certain period of time.

DOI: https://doi.org/10.2478/bhee-2021-0022 | Journal eISSN: 2566-3151 | Journal ISSN: 2566-3143
Language: English
Page range: 86 - 94
Submitted on: Oct 1, 2021
Accepted on: Nov 1, 2021
Published on: Oct 26, 2022
Published by: Bosnia and Herzegovina National Committee CIGRÉ
In partnership with: Paradigm Publishing Services
Publication frequency: 2 issues per year

© 2022 Senad Hadžić, Husnija Ferizović, Obrad Skrba, Adnan Muharemović, Bojan Rebić, published by Bosnia and Herzegovina National Committee CIGRÉ