Impact of Water Mist Extinguisher Construction on Parameters of Generated Drops Cover

Impact of Water Mist Extinguisher Construction on Parameters of Generated Drops

By: Jan KAŹMIERAK  
Open Access
|Jan 2021

Abstract

The paper analyses the impact that the construction of water mist extinguishers exerts on the size of generated drops. The test was based on the examination of three extinguishers of two producers, which have been available in the market in recent years.

The test was carried out with the use of the IPS Drop Spectrum Analyzer (DSA). The device operates by using the photoelectric method to measure the parameters of the extinguishing stream microstructure. There were two measuring ranges: 0÷1 414 µm and 0÷2 658 µm.

The test results present mean diameters of the generated drops, aggregated curves representative of their share as well as the analysis of the quality of spraying the extinguishing medium. The tests have shown that two out of three tested extinguishers do not generate water mist with standard parameters at a distance of 170 cm. The smallest mean diameters of drops were generated by extinguisher B, whereas the biggest ones by extinguisher C The highest level of spraying among all samples was found for extinguisher B. It’s Sauter diameter mean amounted to 564.03 µm. Further, it was shown what impact the construction of water mist extinguishers exerts on the size of generated drops.

DOI: https://doi.org/10.21307/acee-2020-034 | Journal eISSN: 2720-6947 | Journal ISSN: 1899-0142
Language: English
Page range: 99 - 104
Submitted on: Oct 30, 2020
Accepted on: Nov 23, 2020
Published on: Jan 27, 2021
Published by: Silesian University of Technology
In partnership with: Paradigm Publishing Services
Publication frequency: 4 issues per year

© 2021 Jan KAŹMIERAK, published by Silesian University of Technology
This work is licensed under the Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 License.