This study deals with the Fire Growth Rate Index (FIGRA) as a key fire characteristic of electrical cables (determined by a cone calorimeter) that allows to estimate their reaction to fire class. Three power (supply) electrical cables (reaction to fire class B2ca) were tested by a cone calorimeter using different heat fluxes of 20, 30, 40 a 50 kW·m−2. The cables were three-wire (cross-section of each wire was 1.5 mm2) with a nominal voltage of 0.6 kV (alternating current), resp. 1 kV (direct current). The cable sheaths were made of an ethylene copolymer filled with aluminum hydroxide. The beddings were made of an ethylene copolymer filled with a mixture of aluminum hydroxide and calcium carbonate. The conductor insulations of one electrical cable were made of crosslinked polyethylene and the conductor insulations of the other two electrical cables were made of an ethylene copolymer filled with aluminum hydroxide. FIGRA was determined per unit length and unit area of electrical cables. FIGRA increased with increasing heat flux. At a heat flux of 50 kW·m−2, all the electric cables examined showed a very similar FIGRA (from 0.19 to 0.21 kW·m−1·s−1 and 18.4 to 21.2 kW·m−1·s−1, respectively). Conversely, at a heat flux of 20 kW·m−2, the investigated cables showed greater FIGRA variance (in the range of 0.11 to 0.16 kW·m−1·s−1 or 10.8 to 16.2 kW·m−1·s−1).

Language: English
Page range: 81 - 90
Submitted on: Apr 20, 2021
Accepted on: May 26, 2021
Published on: Aug 5, 2021
Published by: Slovak University of Technology in Bratislava
In partnership with: Paradigm Publishing Services
Publication frequency: 2 times per year

© 2021 Jozef Martinka, Peter Rantuch, Igor Wachter, Tomáš Štefko, Martin Trčka, Martina Hladová, Aleš Nečas, Janka Sulová, published by Slovak University of Technology in Bratislava
This work is licensed under the Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 License.