Seismic Behaviour of Long Links in Eccentrically Braced Frames Strengthened with Steel Plate and Diagonal Stiffener Cover

Seismic Behaviour of Long Links in Eccentrically Braced Frames Strengthened with Steel Plate and Diagonal Stiffener

Open Access
|Sep 2026
Read online

Figures & tables

Figure 1:

Differences in the behaviour of the three models of steel structural systems (Yurisman, Budiono, Moestopo, & Suarjana, 2010) (Daneshmand & Hashemi, 2012) (Yurisman, Sari, Murdiansyah, Chairi, & Khadavi, 2025)

Figure 2:

Configurations of Eccentrically Braced Frames and link yielding mechanism (ANSI/AISC & 341-16., 2016) (Yurisman, Sari, Murdiansyah, Chairi, & Khadavi, 2025) (Azad & Topkaya, 2017)

Figure 3:

Long link in EBF Portal (Nastran, 2023) (Chairi, Zaidir, Haris, & Yurisman, 2023)

Figure 4:

Link Classification, modified from (Bruneau, Uang, & Whittaker, 2011)

Figure 5:

Deformation of link (free body diagram), modified from (Bruneau, Uang, & Whittaker, 2011)

Figure 6:

Steel profile used for specimens (modified of (Yurisman, Budiono, Moestopo, & Suarjana, 2010)

Table 1:

Test specimen specification

IDModified Links
Flange end thickening (1/3 L) [mm]Midspan diagonal stiffener (1/3 L) [mm]End diagonal stiffener plate (1/3 L) [mm]
LL-0---
LL-18--
LL-288-
LL-38-8
LL-4888
Figure 7:

Test specimen details

Figure 8:

The constructed dimensions for testing specimens with an endplate (Isometri)

Figure 9:

Reference loading protocol for link beams (ANSI/AISC & 341-16., 2016)

Figure 10:

Experimental loading protocol, adopted from (ANSI/AISC & 341-16., 2016)

Figure 11:

Initial test setup planning

Figure 12:

Finite Element Modelling for Long Link (Chairi, Zaidir, Haris, & Yurisman, 2023)

Figure 13:

Visual inspection of experimental outcomes

Table 2:

Test specimen condition overview

NoIDYield7B Cycle (0.03 rad)UltimateFailure
CycleDisplac ement [mm]P [kN]CycleDisplac ement [mm]P [kN]CycleDisplac ement [mm]P [kN]CycleDisplac ement [mm]P [kN]
1LL-06A19.2672.367B29.0485.6610A67.20107.8010B67.2060.68
2LL-16B19.3083.247B28.89106.848B38.40116.008B34.86106.02
3LL-26B19.4179.507B28.83102.549A48.00124.309B48.0069.60
4LL-36B19.3278.347B28.92100.607B28.80100.608A38.4067.72
5LL-46B19.1784.047B28.80109.207B28.80109.208A38.3064.80
Figure 14:

Experimental test backbone curve

Table 3:

Specimens Strength Capacity (Control and Modification)

Specimens ModificationsYield7B Cycle (0.03 rad)
Load [kN]Specimens ControlLoad [kN]EnhancementLoad [kN]Specimens ControlLoad [kN]Enhancement
LL-183.24LL-072.3615.04%106.84LL-085.6624.73%
LL-279.50LL-072.369.87%102.54LL-085.6619.71%
LL-378.34LL-072.368.26%100.60LL-085.6617.44%
LL-484.04LL-072.3616.14%109.20LL-085.6627.48%
Figure 15:

Experimental test backbone curve

Table 4:

Test specimen stiffness coefficient

IDConditionDisplacement [mm]Rotation Angle [rad]Load [kN]Stiffness [N/m]
LL-0Initial yielding19.260.0272.363.76
Cycle 7B29.040.0385.662.95
LL-1Initial yielding19.300.0283.204.31
Cycle 7B28.890.03107.003.70
LL-2Initial yielding19.410.0279.304.01
Cycle 7B28.830.03102.003.56
LL-3Initial yielding19.320.0277.304.05
Cycle 7B28.920.03101.003.48
LL-4Initial yielding19.170.0283.504.38
Cycle 7B28.800.03109.003.79
Figure 16:

Experimental specimen stiffness curve

Table 5:

Experimental ductility ratio of test specimen

IDConditionDisplacement [mm]Rotation Angle [rad]Load [kN]dy [mm]du [mm]µµ Average
LL-0 (+)Yield19.220.0271.5819.2229.011.511.51
7B Cycle29.010.0385.50
LL-0 (–)Yield–19.260.02–72.36–19.26–29.041.511.51
7B Cycle–29.040.03–85.66
LL-1 (+)Yield16.680.0274.8616.6826.531.591.55
7B Cycle26.530.03104.58
LL-1 (–)Yield–19.300.02–83.24–19.3–28.891.501.55
7B Cycle–28.890.03–106.84
LL-2 (+)Yield19.260.0278.5219.2628.831.501.50
7B Cycle28.830.03102.54
LL-2 (–)Yield–19.410.02–79.50–19.41–28.861.491.50
7B Cycle–28.860.03–102.30
LL-3 (+)Yield19.260.0262.0219.2628.861.501.50
7B Cycle28.860.0388.70
LL-3 (–)Yield–19.320.02–78.34–19.32–28.921.501.50
7B Cycle–28.920.03–100.60
LL-4 (+)Yield19.300.0271.1619.3028.831.491.50
7B Cycle28.830.03105.40
LL-4 (–)Yield–19.170.02–84.04–19.17–28.81.501.50
7B Cycle–28.800.03–109.20
Figure 17:

Experimental specimen ductility curve

Figure 18:

Experimental hysteretic loop and energy dissipation capacity at loading Cycle 7B

Table 6:

Specimen energy dissipation based on hysteresis loop area

IDCycle Area 7B [kN · m]Cumulative Dissipated Energy [kN · m]Ratio (Cycle Area 7B/Cumulative Dissipated Energy)
LL-02.456.550.37
LL-11.985.080.39
LL-21.314.450.29
LL-31.304.340.30
LL-41.194.500.27
DOI: https://doi.org/10.2478/cee-2026-0076 | Journal eISSN: 2199-6512 (formerly 1336-5835) | Journal ISSN: 1336-5835
Language: English
Page range: 1204 - 1223
Submitted on: Oct 29, 2025
Accepted on: Jan 2, 2026
Published on: Sep 22, 2026
Published by: University of Žilina
In partnership with: Paradigm Publishing Services
Publication frequency: 4 issues per year

© 2026 Maiyozzi Chairi, Sabril Haris, Rendy Thamrin, Yurisman, published by University of Žilina
This work is licensed under the Creative Commons Attribution 4.0 License.