Assessment of bioaerosols in tuberculosis high-risk areas of health care facilities in central Thailand Cover

Assessment of bioaerosols in tuberculosis high-risk areas of health care facilities in central Thailand

Open Access
|Apr 2019

Figures & Tables

Table 1

Indoor bacterial and fungal concentrations in TB high-risk areas based on environmental parameters and other potential contributors

Data for TB high-risk areas Median (IQR), unless indicated otherwiseEmergency department (n = 27)TB ward (n = 47)Bronchoscopy unit (n = 7)TB clinic (n = 18)All areas (n = 99)
Air change rate (h–1)6.0 (5.9–6.2)6.7 (6.1–7.3)7.0 (5.2–7.1)6.3 (5.2–7.0)6.2 (6.0–7.1)
Temperature (°C)25.6 (25.1–27.1)31.5 (29.1–32.0)24.6 (24.2–25.7)28.3 (26.3–30.7)27.9 (25.3–31.5)
Relative humidity (%)61.7 (60.0–63.7)66.7 (57.8–70.1)57.2 (53.8–66.3)68.2 (58.2–70.6)62.2 (57.8–70.0)
TB infection control score24.0 (21.0–28.0)26.0 (22.0–28.0)21.0 (14.0–25.0)27.0 (23.8–28.0)26.0 (22.0–28.0)
Good level, frequency (%)23.0 (85.2)37.0 (78.7)4.0 (57.1)16.0 (88.9)80.0 (80.8)
Moderate level, frequency (%)4.0 (14.8)10.0 (21.3)3.0 (42.9)2.0 (11.1)19.0 (19.2)
Daily number of occupants in each area35.0 (15.0–60.0)7.0 (5.0–10.0)6.0 (5.0–15.0)20.0 (6.8–69.3)10.0 (5.0–30.0)
Daily number of active TB patient(s) in each area1.0 (1.0–1.0)1.0 (0.0–1.0)2.0 (1.0–7.0)1.0 (0.0–1.0)
Daily number of coughs by TB patient(s) not1.0 (0.0–1.0)3.0 (1.0–3.0)0.0 (0.0–1.0)
wearing a protective mask in each area
Ventilation system
Natural ventilation, frequency (%)2.0 (7.4)37.0 (78.7)8.0 (44.4)47.0 (47.5)
Central-type air conditioner, frequency (%)12.0 (44.4)7.0 (38.9)19.0 (19.2)
Split-type air conditioner, frequency (%)13.0 (48.2)10.0 (21.3)7.0 (100.0)3.0 (16.7)33.0 (33.3)
Indoor airborne bacteria (cfu/m3)691.0 ± 79.61533.8 ± 132.50567.9 ± 208.55627.2 ± 124.60596.1 ± 140.90
Indoor airborne fungi (cfu/m3)618.4 ± 108.03464.7 ± 130.11478.1 ± 178.01539.7 ± 129.59521.2 ± 142.20

[i] IQR, interquartile range; SD, standard deviation; TB, tuberculosis

Good level = score 21–30 score; moderate level = score 11–20; poor level = score 0–10

cfu/m3: colony forming unit per cubic meter, mean ± SD

Figure 1

Concentrations of airborne bacteria and fungi, indoors (black bars) and outdoors (gray bars), in the emergency department, TB clinic, bronchoscopy unit, TB ward, and all areas (total). Error bars indicate SD from the mean (indicated above bars). SD, standard deviation; TB, tuberculosis

Figure 2

Size distributions of indoor airborne bacteria and fungi in emergency department, TB clinic, bronchoscopy unit, TB ward, and all areas (total). Median concentration (cfu/m3) at each Andersen impactor stage is indicated within the stacked bars. The stages are coded according to the key at the bottom of the Figure.

TB, tuberculosis

Table 2

Comparison of factors and indoor airborne bioaerosol concentration using linear regression

FactorBacteria (cfu/m3)Fungi (cfu/m3)
B95% CI (lower, upper)PBa95% CI (lower, upper)P
Air change rate (h–1)–71.30–87.54, –55.06<0.001***–71.64–88.09, –55.19<0.001***
Temperature (°C)–5.54–14.77, 3.690.24–4.36–13.70, 4.990.36
Relative humidity (%)6.662.20, 11.120.004**6.071.53, 10.610.009**
TB infection control score–3.39–10.48, 3.070.35–4.77–11.89, 2.360.19
Daily number of patients with active TB (in each area)–8.69–19.24, 1.850.11–9.03–19.66, 1.610.095
Daily number of occupants in each area1.810.75, 2.870.001**1.820.75, 2.890.001**
Daily number of coughs by TB patients14.812.14, 27.470.022*10.40–2.56, 23.370.14
(not wearing a protective mask) Department
Emergency department130.4972.77, 188.22<0.001***133.5975.50, 191.67<0.001***
TB clinic and bronchoscopy unit19.42–45.48, 84.330.551.68–63.95, 67.300.96
Ventilation system§
Central-type air conditioner166.08102.63, 229.53<0.001***164.41100.03, 228.78<0.001***
Split-type air conditioner–46.27–105.46, 12.930.12–53.67–113.17, 5.840.077

[i] The mean indoor airborne bacteria and fungi (cfu/m3 = colony forming unit per cubic meter)

Emergency department (TB clinic and bronchoscopy unit, and TB ward = 0, Emergency department = 1), TB clinic and bronchoscopy unit

(Emergency department and TB ward = 0, TB clinic and bronchoscopy unit = 1)

§Central type air conditioner (natural ventilation and split type air conditioner = 0, central type air conditioner = 1), Split type air conditioner (natural ventilation and central type air conditioner = 0, split type air conditioner = 1)

*P < 0.05

**P < 0.01

***P < 0.001

Table 3

Comparison of factors and indoor airborne bioaerosol concentration using multiple linear regression

FactorsBacteria (cfu/m3)Fungi (cfu/m3)
B95% CI (lower, upper)PB95% CI (lower, upper)P
Air change rate (h–1)–50.48–64.99, –35.97<0.001***–51.57–66.66, –36.48<0.001***
Relative humidity (%)7.274.25, 10.29<0.001***6.593.44, 9.73<0.001***
Emergency department65.0521.99, 108.120.003**68.3723.58, 113.150.003**
Central-type air conditioner§113.9063.60, 164.190.001**107.3855.08, 159.68<0.001***
Constant429.84191.73, 667.960.001405.80158.18, 653.420.002

[i] The mean indoor airborne bacteria and fungi (cfu/m3 = colony forming unit per cubic meter)

Emergency department (TB clinic and bronchoscopy unit, and TB ward = 0, Emergency department = 1), TB clinic and bronchoscopy unit

(Emergency department and TB ward = 0, TB clinic and bronchoscopy unit = 1)

§Central type air conditioner (natural ventilation and split type air conditioner = 0, central type air conditioner = 1), split type air conditioner (natural ventilation and central type air conditioner = 0, split type air conditioner = 1)

Model bacteria (cfu/m3) r2 = 0.636, model fungi (cfu/m3) r2 = 0.614

*P < 0.05

**P < 0.01

DOI: https://doi.org/10.1515/abm-2019-0002 | Journal eISSN: 1875-855X | Journal ISSN: 1905-7415
Language: English
Page range: 55 - 63
Published on: Apr 30, 2019
Published by: Chulalongkorn University
In partnership with: Paradigm Publishing Services

© 2019 Jarmmaree Sornboot, Wichai Aekplakorn, Pongrama Ramasoota, Surat Bualert, Somying Tumwasorn, Wiroj Jiamjarasrangsi, published by Chulalongkorn University
This work is licensed under the Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 License.