Skip to main content
Have a personal or library account? Click to login
A magnetic-core based fault current limiter for utility applications Cover

A magnetic-core based fault current limiter for utility applications

Open Access
|Sep 2011

Abstract

A magnetic core fault current limiter (MFCL) saturated by a dc biasing coil was designed and implemented, both experimentally and in PSCAD/EMTDC simulation package. The operation of the device under normal operating conditions and faults was then studied. A case study was carried out using simulation to demonstrate the application of the proposed MFCL. The benefits of using a grid-connected single-phase rectifier to bias the dc coil of the MFCL were investigated through simulation studies. The simulation results show improvements in limiting the fault current and minimizing the voltage sag on healthy busbars during a fault. It was also found that the highest improvements are achieved when the rectifier is connected to the downstream grid.

Keywords:  Distributed generators, distribution network, magnetic fault current limiter.

Doi: 10.4038/jnsfsr.v39i3.3626

J.Natn.Sci.Foundation Sri Lanka 2011 39 (3):227-234

Language: English
Page range: 227 - 234
Published on: Sep 27, 2011
Published by: National Science Foundation of Sri Lanka
In partnership with: Paradigm Publishing Services

© 2011 S.K. Abeygunawardane, J.R.S. Sisira Kumara, J.B. Ekanayake, A. Arulampalam, published by National Science Foundation of Sri Lanka