Have a personal or library account? Click to login
Controlled Switching of the T402 Transformer in the Križovany 400kV Substation Cover

Controlled Switching of the T402 Transformer in the Križovany 400kV Substation

Open Access
|Jun 2011

Abstract

The paper deals with simulating the circumstances of switching surge and trigger current at switching-in of the T402 autotransformer recently installed in Križovany, with the tests conducted by means of ATP (Alternative Transient Program) simulation software for simulating transient electromagnetic phenomena. The target has been to determine temporal curves for the most critical surge instances against earth and between the phases and the curves for trigger current with and without surge limiters connected, and to determine by means of simulations the size and statistical frequency of switching surges and based on a controlled switching simulation, to describe the elimination of transient phenomena during the process and in reference to the simulations and to operating manual for the PSD02 Siemens control unit, suggest the required configuration settings for the unit.

DOI: https://doi.org/10.2478/v10187-010-0002-y | Journal eISSN: 1339-309X | Journal ISSN: 1335-3632
Language: English
Page range: 11 - 19
Published on: Jun 7, 2011
Published by: Slovak University of Technology in Bratislava
In partnership with: Paradigm Publishing Services
Publication frequency: 6 issues per year

© 2011 František Janíček, Martin Mucha, Karol Česnek, Jozef Kováčik, published by Slovak University of Technology in Bratislava
This work is licensed under the Creative Commons License.

Volume 61 (2010): Issue 1 (January 2010)