Have a personal or library account? Click to login
PIV measurement of tube-side in a shell and tube heat exchanger Cover

PIV measurement of tube-side in a shell and tube heat exchanger

Open Access
|Apr 2018

Abstract

In order to improve the performance of the shell and tube heat exchanger, a porous baffle and a splitter bar are employed in this research. Through the arrangement of the porous baffle in the tube-side inlet and the splitter bar in the tube, the flow distribution of liquid in the heat exchanger is improved. PIV technology is used to investigate the unsteady flow in the tube-side inlet and the outlet of different models. The porous baffle significantly improves the flow of fluid in the shell and tube heat exchanger, especially by eliminating/minimizing the maldistribution of fluid flow in the tube-side inlet. The performance of the arc baffle is better than that of the straight baffle. The splitter bar has a minimal effect on the flow field of the tube-side inlet, but it effectively improves the flow in the tube bundle and restrains the vortex generation in the tube-side outlet.

Language: English
Page range: 60 - 66
Published on: Apr 16, 2018
In partnership with: Paradigm Publishing Services
Publication frequency: 4 issues per year

© 2018 Kai Wang, Zixu Zhang, Qiong Liu, Xincheng Tu, Hyoung-Bum Kim, published by West Pomeranian University of Technology, Szczecin